PRE-INSULATED
PIPING SYSTEM
(UNDERGROUND PIPING SYSTEM, TERRA-GARD)
TERRA-GARD Piping System
TERRA-GARD
is an underground piping system for distribution of hot or chilled
fluids at temperatures up to 130°C. Every system is pre-engineered
and factory tested before shipment. Carrier pipe is supplied in
customer's choice of materials which include steel, copper, stainless
steel, aluminum, brass, polyvinyl chloride (PVC), and fiberglass
reinforced polyester (FRP). PVC or H.D.P.E. jacketing is standard,
but customer can also specify jacketing of fiberglass reinforced
plastic. Terra-Gard is shipped in 6 meter or 12 meter random lengths,
with 130-150 mm of carrier pipe exposed at unit ends to facilitate
field joining.
BENEFITS
Since 1910, RICWIL has devoted its activities solely to design,
manufacture and installation instructions of preinsulated, prefabricated
piping systems. RICWIL Terra-Gard is an inexpansive underground
distribution system that will provide many years of efficient service.
- Terra-Gard - Single Source for Entire System
Give
RICWIL one purchase order for your Terra-Gard system and received
a complete, engineered preinsulated system; including carrier
pipe, thermal insulation, protective jacketing, fittings and
joining materials to meet customer's requirements. Included
with our total package are engineered installation drawings
and the service of a factory trained field instructor.
- Design Flexibility
RICWIL's Terra-Gard system is
not a stock item, but rather a combination of available material
that meets your specific design requirements.
- Faster Installation
One delivery brings all piping materials-preinsulated and prefabricated,
resulting in less material handling and storage problems. All
units are part-numbered in accordance with installation drawing
for easy identification, resulting an a fast, systematic installation
of your system.
- Reduced Field Cost
A Terra-Gard system is prefabricated to actual
job requirements and dimensions so there is no material wastage.
Prefabrication eliminates field insulating and jacketing.
- Quality Controlled
RICWIL® systems must pass a rigid inspection at our
plant. Preengineered and factory fabricated with modern techniques
by well-trained
fabricators are the customer's assurance of quality. Terra-Gard
systems arrive at the job-site with all insulation protected
from the elements. Insulation remains dry and efficient throughout
shipping, storage, and installation.
- Maximum System Efficiency
All Terra-Gard jackets provide a positive
moisture barrier. Polyurethane foam insulation with its low
K factor along with the jacket material assures minimal system
heat loss or gian. RICWIL Terra-Gard represent the highest product
quality and maximum installation efficiency for all buried hot,
or chilled fluids up to 130°C.

A. CARRIER PIPE
Terra-Gard can be furnished with any carrier
pipe to customer's specification.
The followings are most commonly used carrier pipes.
A.1 Steel pipes |
|
A.1.1 ASTM A 53 Gr.B Std
weight ERW or SEAMLESS |
|
A.1.2 API 5L Gr.B Std weight
ERW or SEAMLESS |
|
A.1.3 JIS G 3454 STPG 38
SCH 40 ERW or SEAMLESS |
|
A.1.4 JIS G 3452 SGP |
|
A.1.5 BS 1387 or DIN2448
ST35 |
A.2 Copper pipe
|
|
A.2.1 ASTM B-88 type M,L,
or K. |
|
A.2.2 JIS H 3300 |
B. INSULATION
B.1 |
Material: Rigid polyurethane
foam injected by foaming machine in one continuous process |
B.2 |
Density : 45kg/m³ CFC
Free |
B.3 |
Thermal Conductivity: 0.02W/m.°K
(0.017 Kcal/m.hr.°C) at 20°C |
B.4 |
Compressive strength: 2.0kg/cm² |
B.5 |
Closed cell Content: min
90% |
B.6 |
Temperature limit: 130°C.
For higher temperature, consult RICWIL engineering department |
B.7 |
Shear strength: 4.0 kg/cm² |
B.8 |
Water permeability: 2.2
perm-inches |
C. JACKET
Terra-Gard can be furnished with any carrier
pipe to customer's specification.
The followings are most commonly used carrier pipes.
C.1 MATERIAL |
|
Standard TERRA-GARD Jacket
material is extruded high density polyethylene black in
colour. |
C.2 QUALITY
|
|
C.2.1 ASTM D 1248 TYPE 4
CLASS 3 |
|
C.2.2. JIS K6761 |
|
C.2.3. BS 3284/1967 TYPE50 |
|
C.2.4. DIN 8074/75 |
C.3 WALL THICKNESS
|
|
Jacket wall thickness varies
from 2.5 mm to 8 mm depending on carrier pipe size. |
D. FITTINGS
D.1 Elbows, tees and anchors. |
|
All accessories, such as
elbows, expansion loops, tees and anchor units, are supllied
preinsulated and prefabricated and are PART-NUMBERED in
accordance with installation drawings.
Allowance for pipe expansion and/or contraction
is provided for at elbows during fabrication at the factory.
Fittings are manufactured with material identical to straight
sections. All carrier pipe weld seams are hydrostatically
tested to at least 17.5 Kg/cm² pressure. Technical
informations will be supplied upon request. |